CVE-2026-11826
Published:July 18, 2026
Updated:August 06, 2026
OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.
Related Resources (4)
Do you need more information?
Contact UsCVSS v4
Base Score:
8.7
Attack Vector
NETWORK
Attack Complexity
LOW
Attack Requirements
NONE
Privileges Required
LOW
User Interaction
NONE
Vulnerable System Confidentiality
HIGH
Vulnerable System Integrity
HIGH
Vulnerable System Availability
HIGH
Subsequent System Confidentiality
NONE
Subsequent System Integrity
NONE
Subsequent System Availability
NONE
CVSS v3
Base Score:
8.8
Attack Vector
NETWORK
Attack Complexity
LOW
Privileges Required
LOW
User Interaction
NONE
Scope
UNCHANGED
Confidentiality
HIGH
Integrity
HIGH
Availability
HIGH
Weakness Type (CWE)
Heap-based Buffer Overflow
EPSS
Base Score:
0.42